ComAp IG-NT Reference Manual page 125

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Setpoint: FuelSol offset
Group
Engine Params
Range [units]
-5.0 .. 5.0 [s]
Related FW
3.0
Description
This setpoint is used for fine adjustment of the moment when the
output is activated. The time is related to the activation of the
where negative values mean the fuel solenoid is activated in advance to the
starter motor and positive values mean the fuel solenoid is delayed after the
starter motor.
N
OTE
This setpoint is taken into accout at diesel engines only, i.e. if the setpoint
solenoid
Setpoint: D+ Function
Group
Engine Params
Range [units]
ENABLED,CHRGFAIL,DISABLED [-]
Related FW
3.0
Description
This setpoint adjusts the function of the D+ terminal.
ENABLED
CHRGFAIL
DISABLED
N
OTE
Some alternators provide a terminal labelled as "L" instead of "D+". It is not
possible to connect this "L" terminal to the "D+" terminal of the controller.
Setpoint: Bin selector 1
Group
Engine params
Range [units]
OFF, ON [-]
Related FW
3.0
Force value
YES
possible
Description
The setpoint is used to switch on and off the output
Setpoint: Bin selector 2
Group
Engine params
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
:
is set to DIESEL ENGINE.
The D+ terminal is used for running engine detection as well
as for charger failure alarm detection.
The D+ terminal is used for charger failure alarm detection
only.
The D+ terminal is not used.
:
Fuel Solenoid
Starter
output,
Fuel
Bin selector
1.
125