Description
The output is closed when the gen-set is ready for operation or is currently in
operation.
Binary output: Ready
Related FW
3.0
Description
The output is closed while the gen-set is not in operation at the moment, however
it is ready to be put into operation. The output is closed while:
Binary output: Not ready
Related FW
3.0
Description
The output is closed while the gen-set is not in operation, however it is not ready
to be put into operation. The output is closed while:
Binary output: CrankProcedure
Related FW
3.0
Description
The output is closed while the engine is cranking and during pauses between
crank attemps. The output is opened either when the gen-set is started or failed to
start. See the diagram in the descrition of the output
between outputs CrankProcedure,
Binary output: Starting
Related FW
3.0
Description
The output is closed at the beginning of the prestart phase and remains closed
during prestart, cranking and starting phases. The output is opened either when
the gen-set goes to running phase or when it failed to start. See the diagram in the
descrition of the output
Binary output: Idle run
Related FW
3.0
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
the genset is not running and
the controller is not in OFF mode and
there isn't any alarm blocking start of the gen-set
the genset is not running and
the controller is in OFF mode or
there is an alarm blocking start of the gen-set.
Cranking
Cranking
Cranking
and Starter.
for details.
for differencies
306