ComAp IG-NT Reference Manual page 166

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Setpoint: Load gain
Group
Sync/Load Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
3.0
Description
This setpoint adjusts the gain factor (P-factor) of the load control PI loop. The
integration factor (I-factor) for the load control loop is adjusted by the setpoint
Load
N
OTE
See the chapter
regulation loops and their adjustment.
Setpoint: Load int
Group
Sync/Load Ctrl
Range [units]
0 .. 100 [%]
Related FW
3.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the load control PI
loop. The gain factor (P-factor) for the load control loop is adjusted by the setpoint
Load
Setpoint: RampStartLevel
Group
Sync/Load ctrl
Range
0 .. 100 [%]
[units]
Related FW
3.0
Description
This setpoint adjusts the load level at which the
been closed. The intention of this setpoint is to give the gen-set certain "loading impulse"
right after closing the GCB to avoid possible oscillations around 0kW or even reverse
power if the ramp begun at 0kW.
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
int.
:
Regulation loops overview
gain.
for general information about
Load ramp
starts after the GCB has
166