Setpoint: #RunHrsMaxDiff
Group
Pwr management
Range [units]
0 .. 65000 [h]
Related FW
3.0
Description
This setpoint adjusts the "deadband" for the
The priorities are swapped not until the relative engine hours (RHE) difference is
higher than this deadband.
Setpoint: #PwrBandContr 1
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#1 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
N
OTE
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 2
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#2 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
N
OTE
The combinations of gensets must be created so, that the total nominal power of
the Power band #1 < #2 < #3 < #4.
Setpoint: #PwrBandContr 3
Group
Pwr management
Range [units]
1, 2, 1+2, 3, 1+3, 2+3, 1+2+3 [-]
Related FW
3.0
Description
This setpoint is used to select the gen-sets which will run within the power band
#3 if the optimalization according to gen-set size is active. Learn more about this
topis in the chapter
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
Gen-set size
:
Gen-set size
:
Gen-set size
running hours equalization
optimalization.
optimalization.
optimalization.
function.