ComAp IG-NT Reference Manual page 152

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Range [units]
LoadResStrt 3
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
mgmt mode
about reserves in the chapter
The currently active reserve set is selected by binary inputs
3
and
N
OTE
The reserve for stop must be always adjusted higher than the reserve for start.
Setpoint: #LoadResStrt 4
Group
Pwr Management
Range [units]
-32000 ..
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in absolute mode. i.e.
mgmt mode
about reserves in the chapter
The currently active reserve set is selected by binary inputs
3
and
N
OTE
If the absolute power management is selected, this setpoint (or the setpoints
LoadResStrt
set is selected) determines also the number of gensets (that are part of the power
management) which will start (according to their priority and nominal power).
N
OTE
There is a possiblity to assign this setpoint negative number. This can be used in
some situations to allow genset start after Sys Start/Stop gets active. It is not
destined for normal operation. Please refer to the Troubleshooting guide for more
information (chapter "MGCB is not closed although gensets are running").
N
OTE
# sign in the name of this setpoint marks that this setpoint is shared among all
controllers connected by CAN2 bus.
Setpoint: #LoadResStop 4
Group
Pwr Management
Range [units]
LoadResStrt 4
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
mgmt mode
about reserves in the chapter
The currently active reserve set is selected by binary inputs
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
.. 32000 [kX]
= ABS (kW) or ABS (kVA) if the reserve set #3 is active. Learn more
Load res
4. If none of these inputs is active the set #1 is selected.
:
LoadResStop 4
[kX]
= ABS (kW) or ABS (kVA) if the reserve set #4 is active. Learn more
Load res
4. If none of these inputs is active the set #1 is selected.
:
1,
LoadResStrt 2
:
:
.. 32000 [kX]
= ABS (kW) or ABS (kVA) if the reserve set #4 is active. Learn more
Reserves, minimal running
Reserves, minimal running
or
LoadResStrt 3
depending on which load reserve
Reserves, minimal running
Pwr
power.
Load res
2,
Load res
Pwr
power.
Load res
2,
Load res
Pwr
power.
Load res
2,
Load res
152

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG-NT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ig-ntcIs-ntIg-eecIg-nt-bbIg-ntc-bbIs-ntc-bb ... Show all

Table of Contents

Save PDF