ComAp IG-NT Reference Manual page 131

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

N
OTE
ENABLED position corresponds to the method how the IG-classic and IS-classic
controllers handled the alarms.
Setpoint: Overspeed
Group
Engine Protect
Range [units]
0 .. 200 [%]
Related FW
3.0
Description
This setpoint adjusts the threshold level for overspeed protection.
N
OTE
The overspeed protection is evaluated all the time and without any delay.
Setpoint: Max+CylDifPmin
Group
Engine protect
-32000 .. +32000 [°C]
Range [units]
Related FW
3.0
This setpoint adjusts the maximum allowed positive difference between a
Description
particular cylinder temperature and average cylinder temperature at minimum
power level adjusted by setpoint PminCylDifEval. This setpoint is one of four
setpoints that define the allowed area of cylinder temperature differencies
depending on gen-set power. See the picture below.
A
LLOWED AREA OF CYLINDER TEMPERATURE DIFFERENCIES DEPENDING ON GENSET
POWER
If the difference of actual cylinder temperature from the average temperature is out
of the allowed range at one or more cylinders the alarm Wrn CylTemp is issued
after the delay
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
blocked.
:
:
CylDifEvalDel
elapses. The alarm is intended for detection that
131