adjusted by setpoint
N
OTE
The default value of minimal running power, which takes place while none of the
inputs MinRun power x, is 0kW.
N
OTE
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
C
AUTION
All controllers cooperating together in Power management must have the same
minimal running power selected.
N
OTE
It is possible to use virtual peripheries for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
bus. See the principial diagram of such distribution in the description of the input
Load res
Binary input: MinRun power 3
Related FW
3.0
Description
This input is used to activate the function Minimal running power #3, which is
adjusted by setpoint
N
OTE
The default value of minimal running power, which takes place while none of the
inputs MinRun power x, is 0kW.
N
OTE
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
C
AUTION
All controllers cooperating together in Power management must have the same
minimal running power selected.
N
OTE
It is possible to use virtual peripheries for distribution of the binary signal from one
physical switch connected to one controller to all other controllers over the CAN
bus. See the principial diagram of such distribution in the description of the input
Load res
Binary input: Priority sw A
Related FW
3.0
Description
This is one of four inputs
D
that can be used for selection of the power management priority externally.
These inputs are optional and if not configured, the priority is then adjusted by the
setpoint Priority.
E
NCODING TABLE
P
RIORITY
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
#MinRunPower
:
:
!
:
2.
#MinRunPower
:
:
!
:
2.
Priority sw
I
A
NPUT
2.
3.
A,
Priority sw
B,
Priority sw C
I
B
I
C
NPUT
NPUT
and
Priority sw
I
D
NPUT
243