ComAp IG-NT Reference Manual page 118

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Setpoint: Prestart time
Group
Engine Params
Range [units]
0 .. 3600 [s]
Related FW
3.0
Force value
YES
possible
Description
This setpoint adjust length of the prestart period before starter is engaged. The
output
you want to disable the prestart function.
Setpoint: Prelubr time
Group
Engine params
Range [units]
0 .. 3600 [s]
Related FW
3.0
Force value
YES
possible
Description
This setpoint is used for adjusting duration of the prelubrication cycle. See the
output
Setpoint: Prelubr pause
Group
Engine params
Range [units]
1 .. 3000 [min]
Related FW
3.0
Force value
YES
possible
Description
YES
This setpoint is used for adjusting the pause between two consequent
prelubrication cycles. See the output
Setpoint: MaxCrank Time
Group
Engine Params
Range [units]
1 .. 240 [s]
Related FW
3.0
Force value
YES
possible
The setpoint adjusts the maximum duration the
Description
one cranking cycle. If there is none of running engine symptoms activated within
this period the particular cranking attempt is finished and either a
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
Prestart
is active during the prestart period. Adjust the setpoint to zero if
Prelubr pump
for details about prelubrication.
Prelubr pump
for details about prelubrication.
starter motor
is energized within
cranking pause
118