ComAp IG-NT Reference Manual page 256

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Binary input: IssueActCallC3
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the channel
#3. Type of the channel is to be adjusted by the setpoint AcallCH3-Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
Binary input: IssueActCallC4
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the channel
#4. Type of the channel is to be adjusted by the setpoint AcallCH4-Type.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
Binary input: IssueActCallC5
Related FW
3.0
Description
This input forces the controller to issue an active call/e-mail/SMS via the channel
#5. Type of the channel is to be adjusted by the setpoint AcallCH4-Addr.
This input can be used to inform a remote user about a specific non-alarm
situation, e.g. mains failure and/or mains return:
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
1. Select a binary signal in the controller, which indicates, that the particular
situation occured, about which you want to be informed remotely. There
are many predefined binary informations provided directly by the
controller or use PLC functions to create the desired binary signal.
2. Configure an universal protection block to the binary signal mentioned
above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary input
IssueActCallC3.
1. Select a binary signal in the controller, which indicates, that the particular
situation occured, about which you want to be informed remotely. There
are many predefined binary informations provided directly by the
controller or use PLC functions to create the desired binary signal.
2. Configure an universal protection block to the binary signal mentioned
above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary input
IssueActCallC4.
1. Select a binary signal in the controller, which indicates, that the particular
situation occured, about which you want to be informed remotely. There
are many predefined binary informations provided directly by the
controller or use PLC functions to create the desired binary signal.
2. Configure an universal protection block to the binary signal mentioned
above and select protection type AL indication.
3. Configure the binary signal mentioned above onto the logical binary input
256

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IG-NT and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Ig-ntcIs-ntIg-eecIg-nt-bbIg-ntc-bbIs-ntc-bb ... Show all

Table of Contents

Save PDF