ComAp IG-NT Reference Manual page 130

Inteli new technology modular gen-set controller, multiple internal engines application - sw configuration mint
Hide thumbs Also See for IG-NT:
Table of Contents

Advertisement

Setpoint: ForceBlockDel1
Group
Engine protect
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as Force block #1 are started to be
evaluated.
Setpoint: ForceBlockDel2
Group
Engine protect
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as Force block #2 are started to be
evaluated.
Setpoint: ForceBlockDel3
Group
Engine protect
Range [units]
0.0 .. 60.0 [s]
Related FW
3.0
Force value
YES
possible
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as Force block #3 are started to be
evaluated.
Setpoint: ResetActAlarms
Group
Engine protect
Range [units]
[-]
Related FW
3.0
Description
DISABLED
ENABLED
Inteli NT MINT, SW Version 3.0, ©ComAp –May 2013
IGS-NT-MINT-3.0 Reference Guide.PDF
Pressing of the fault reset button (at any terminal or external
button) resets only inactive alarms. Active alarms remain in
the alarmlist unchanged and must be reset again when they
become inactive.
Pressing of the fault reset button (at any terminal or external
button) resets all alarms that are currently present in the alarm
list. Inactive alarms disappear from the alarm list immediately,
active alarms are changed to "confirmed" state and disappear
when the alarm condition disappear or the alarm starts to be
Force block 1
has been
Force block 2
has been
Force block 3
has been
130