Setting Of Air Pressure Switch (Only Applicable To Type S) - ABB DressPack Product Manual

Table of Contents

Advertisement

2.10.4 Setting of air pressure switch (only applicable to type S)

General
The digital pressure switch monitors the shop floor air pressure.
Settings
The procedure below details how to set the digital pressure switch. The example
shows how to set according to the pre-set values. The sensor will set g1_air_ok
in the robot controller when pressure reaches 0.5 MPa and reset g1_air_ok if
pressure goes lower than 0.45 MPa.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Product manual - DressPack/SpotPack IRB 8700
3HAC055802-001 Revision: B
2.10.4 Setting of air pressure switch (only applicable to type S)
Mode
Action
Preparation
Make sure that the pressure switch is connected
to 12-24 VDC power.
Initialize
In measurement mode, press SET button for two
seconds or more.
Selection of Unit
Press UP or DOWN button until the display
matches the figure on the right, then press the
SET button.
OUT1 Output
Press UP or DOWN button until display matches
type Setting
the figure on the right, then press the SET but-
ton.
OUT2 Output
Ignore and press the SET button.
type Setting
Response Time
Press UP or DOWN button until display matches
Setting
the value on the right, then press the SET button.
Auto/Manual
Press UP or DOWN button until display matches
Setting
the value on the right, then press the SET button.
Value Setting
In measurement mode, press the SET button.
Set Point Value
When the display blinks, press UP or DOWN
for OUT1(1)
button without pressing the SET button.
Pressure OK
Press UP or DOWN button until the display
goes high
matches the value on the right, then press the
SET button.
Set Point Value
When the display blinks, press UP or DOWN
for OUT1(2)
button without pressing the SET button.
Pressure OK
Press UP or DOWN button until the display
goes low
matches the value on the right, then press the
SET button.
Set Point Value
Ignore and press the SET button.
for OUT2(1)
Set Point Value
Ignore and press the SET button.
for OUT2(2)
The pressure switch changes to measurement
mode. All settings are completed.
Zero Clear Func-
Press UP and DOWN buttons simultaneously
tion
for about 2 seconds, under atmospheric pres-
sure.
© Copyright 2015-2017 ABB. All rights reserved.
2 Installation
Note
0
PA
PA indicates MPa.
1no
("1no" = Output 1
normally open)
2n*
24
ñAn
(ñAn indicates
manual setting)
P_1
0.500
P_2
0.450
P/n3
P/n4
0
0
Continues on next page
133