10.4 Simulation of detector states

Under this menu point, the state of addressable detectors of the series 9200 and IQ8Quad (no esserbus
transponder) can be simulated for test purposes. In all non-addressable detectors (Series 9000 / ES Detect), the
detector zone state is simulated. With the simulation of a detector state for test purposes, all programmed displays
and controls corresponding to this detector and state in the Customer data of the Fire Alarm Control Panel are
activated.
Self-control of the detectors series 9200 / 9200 / IQ8Quad
An intelligent fire detector can be operated in connection with a detector base output (relay or open collector). If
a control has not been programmed in the Customer data of the Fire Alarm Control Panel for this detector, the
integrated detector base output is activated during the simulation of the "Alarm" state.
Detector simulation
:
Zone
Detector :
Status
Fig. 88: Entering the zone and detector number
Detector simulation
: 12
Zone
Detector : 20
Status
Fig. 89: Selection of the detector status for simulation
Enter the zone and detector number of the fire detector or technical alarm module.
Press the >Select< function key.
Enter the number for the desired function ( 1 = Alarm, 2 = Pre-alarm, 3 =Trouble, 4 = End test) or select with
the cursor keys and press the function key >function< to acknowledge the input.
To end this simulation
Each individual detector (or zone) whose operating state has been simulated must be terminated with the
>End test< function!
This function pertains exclusively to the detectors of this (local) control panel. The simulation of
detector states in the essernet
not supported via communications transponder (Part No. 808615) of the 8010 extinguishing control
system.
Dependant on the customer data programming, the master box and any other external alarm devices
are activated during the state simulation of a fire detector.
102
Alarm
Pre-alarm
Trouble
End test
Repeat
Select
1
Alarm
2 Pre-alarm
3 Trouble
4 End test
Function
®
network is impossible. Simulation of individual detectors or zones is
*
By pressing the >Repeat< key,
the displayed detector number is
incremented by the value "+1",
without the need of entering the
number of the new (next higher)
zone/detector number on the
keyboard.
FB 798951.10.GB0 / 04.15
®

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esser iq8control m

Table of Contents