This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly,
especially if you are installing a GWF-7075 panel for the first time.

3.1 Inventory

When you receive the GWF-7075 shipment, be sure to check and verify that the following components were included in the shipment.
Check that all the parts are included in the shipment. The shipment consist of one of each of the following:
main circuit board with display
backbox with door
plastic bag containing two keys, screws, cables, and ten 4.7K ohm end-of-line resistors
manual

3.2 Environmental Specifications

It is important to protect the GWF-7075 control panel from water. To prevent water damage, the following precautions should be FOL-
LOWED when you install the units:
Intended for indoor use in dry locations only.
Do not mount directly on exterior walls, especially masonry walls (condensation).
Do not mount directly on exterior walls below grade (condensation).
Protect from plumbing leaks.
Protect from splash caused by sprinkler system inspection ports.
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery).
When you select a location to mount the GWF-7075 fire alarm control panel, install the unit in a location where it will NOT be exposed
to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.

3.3 Software Downloads

To supply the latest features and functionality in fire alarm and life safety technology to our customers, the Manufacturer makes fre-
quent upgrades to the embedded software in the products. To ensure that you install and program the latest features, the Manufacturer
strongly recommend that you download the most current version of software for each product prior to commissioning any system. If you
have questions about the software and the most recent version for a specific application, contact Technical Support . To download the
HFSS Honeywell Fire Software Suite, you must obtain Customer Training from a Certified Trainer is available at
www.gamewell-fci.com.
Electrical Specifications
Table 3.1 list the terminal block on the GWF-7075 as well as a description of the each individual terminal and their respective electrical
rating. For the location of the terminals, refer to Figure 3.2. See also Section 4 for installation.
Terminal No.
Terminal Block 3
Terminal Block 2
Terminal Block 2
P8
*
Regulated NAC application. When programmed for releasing, NAC are Special Application.
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019

Section 3: Installation Instructions Criteria

Label
Group
Individual
TELCO 1
RING
TIP
PHONE 1
RING
TIP
TELCO 2
RING
TIP
PHONE 2
RING
TIP
RELAY 1
NO
COM
NC
RELAY 2
NO
COM
NC
TROUBLE
NO
COM
NC
SLC IN
+
SLC OUT
+
SLC PROG
+
SBUS
+
A
B
NAC1*
+
NAC2*
+
EXT. Comm
B
Cellular Connection
A
S+
S-
Table 3.1 Terminal Descriptions and Electrical Specifications
Description
Phone Line 1 Telco Ring
Phone Line 1 Telco Tip
Phone Line 1 Phone Ring
Phone Line 1 Phone Tip
Phone Line 2 Telco Ring
Phone Line 2 Telco Tip
Phone Line 2 Phone Ring
Phone Line 2 Phone Tip
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Normally open relay contact
Common terminal
Normally closed relay contact
Used for Class A installations
SLC terminals
Used for programming SLC
Detectors
SBUS Power
SBUS Communication
Notification Appliance
Circuit/Auxiliary power
Notification Appliance
Circuit/Auxiliary power
Cellular Transmitter
Rating
Voltage
Current
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
27.4 VDC
2.5 A, resistive
32 VDC
100 mA
32 VDC
100 mA
32 VDC
100 mA
27.4 VDC
0.5 A
5 VDC
100 mA
27.4 VDC
1 Amp NAC or
Aux power
27.4 VDC
1 Amp NAC or
Aux power
input
55 mA, 95 mA
13