Led Description; Installation Instructions; Mounting The Ske-Srm Cabinet - Honeywell Silent Knight SKE Series Installation And Operation Manual

Voice evacuation
Table of Contents

Advertisement

SKE-Series Voice Evacuation System Installation/Operation Manual
7.2

LED Description

LED
Green
Yellow
7.3

Installation Instructions

This section contains the information needed to properly install the SKE-SRM.
7.3.1

Mounting the SKE-SRM Cabinet.

It is important to protect the SKE-SRM control panel from water. To prevent water damage,
the following conditions should be avoided when installing the units:
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the SKE-SRM cabinet, the unit should be mounted where
it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or
humidity outside the range of 10%-85% at 30°C (86°F) noncondensing.
Follow these steps to mount the remote microphone cabinet:
1. Remove the SKE-SRM from it's packing container.
2. Unlock the cabinet and remove the cabinet door.
3. Unplug microphone from microphone connector. See Figure 7-1.
Place microphone in a safe location while completing cabinet installation.
4. Remove the cover plate by un-screwing the four cover plate screws (see Figure 7-1). Set
the screws aside for later use.
5. Remove the remote microphone chassis assembly by un-screwing the two chassis assem-
bly screws. See Figure 7-2.
Important!
The electronic components on the control panel are sensitive to electrostatic discharge
(static electricity). Wear a grounding strap when handling the control board.
7-2
State
On
Remote microphone has DC power.
Off
Remote microphone has no power or has a major
malfunction.
On
No microphone attached to the unit.
Off
Microphone is connected.