The 11-, 12-, 13- and 15-bit resolutions + sign are shown in the following table. Each analog
value is entered left-justified in the ACCU. The bits marked with "x" are set to "0".
Table 13-11 Measured-value resolution of the analog values (SIMATIC S7 format)
11+VZ
12+S
13+S
15+S
Note
This resolution does not apply for temperature values. The converted temperature values are
the result of a conversion in the analog electronic module.
13.8.3

Measuring ranges of the analog input modules in S7 format

Introduction
The tables in this section contain the digitized analog values for the measuring ranges of the
analog input modules.
The binary representation of the analog values is always the same, so these tables only
compare the measuring ranges and the units.
Measuring ranges for voltage: ± 80 mV
Table 13-12 SIMATIC S7 format: Measuring range ±80 mV
Measuring range ± 80
mV
> 94.071
94.071
80.003
80.000
60.000
- 60.000
- 80.000
ET 200iSP
Operating Instructions, 11/2017, A5E00247483-07
Resolution i
n Bits
decimal
16
8
4
1
Units
decimal
32767
32511
:
27649
27648
20736
:
-20736
-27648
Units
hexadeci‐
mal
10
S 0 0 0 0 0 0 0
H
8
S 0 0 0 0 0 0 0
H
4
S 0 0 0 0 0 0 0
H
1
S 0 0 0 0 0 0 0
H
hexadecimal
7FFF
H
7EFF
H
:
6C01
H
6C00
H
5100
H
:
AF00
H
9400
H
Analog electronic modules
13.8 Representation of analog values
Analog value
High byte
0 0 0 1 x x x x
0 0 0 0 1 x x x x
0 0 0 0 0 1 x x
0 0 0 0 0 0 0 1
Range
Overflow
Overrange
:
:
Nominal range
Low byte