Binary Input (Pulse)

BI_PULSE (SIMATIC Manager hardware catalog)
Pulse binary input = input for detecting/processing continuous status changes in
applied signals.
A floating contact or electronic switch is connected with the binary pulse input. The
object carries out a cyclical check at the input. Every change from one stable status
to the other is detected.
Note
If the Profinet communication is missing, a short pulse is indicated with the
relevant LED for each pulse at the input.
4.2.1

Pulse Length

Parameter for defining the pulse length.
Value range
Unit
0..255
0.1 s
4.2.2

Contact

Parameters for defining the contact type.
Possible values
Description
NO Contact
"Not Open" contact
NC Contact
"Not Closed" contact
Status
NO contact
Contact position
LED
indication
Contact closed >
Pulse
open
0 > 1 > 0
Contact open >
0
closed
TX-I/O PROFINET BIM V1.0
Parameters
NC contact
Process
LED
value
indication
Pulse
0
0 > 1 > 0
0
Pulse
0 > 1 > 0
Process
value
0
Pulse
0 > 1 > 0
27 / 94