Operating the ET 200S on a grounded supply

In this section, you will find information on the overall setup of an ET 200S distributed I/O
system on a grounded supply (TN-S system). The specific subjects discussed are:
● Circuit-breaking devices, short-circuit and overload protection according to DIN VDE 0100
and DIN VDE 0113
● Load power supplies and load circuits
Components and protective measures
Various components and protective measures are prescribed when setting up an entire
plant. The types of component and the degree to which the protective measures are binding
depend on the DIN VDE regulation that applies to your plant setup. The following table refers
to the configuration illustration below:
Table 3- 1
Components and pro-
tective measures
Circuit-breaking device
for PLC, sensors and
actuators
Short-circuit and over-
load protection:
grouped for sensors
and actuators
Load power supply for
AC load circuits with
more than five elec-
tromagnetic devices
EIP-200S Ethernet/IP Adapter Distributed I/O System
System Manual, 06/2018, A5E44345053-AB
Comparison of the DIN VDE 0100 and the DIN VDE 0113
Refer to configuration
illustration
3.7 Operating the ET 200S on a grounded supply
DIN VDE 0100
Part 460:
Main switch
Part 725:
Single-pole protection
of circuits
Isolation by transformer
recommended
Installation and wiring
DIN VDE 0113
Part 1:
Disconnector
Part 1:
With a grounded
secondary circuit:
single-pole protec-
tion
In all other cases:
all-pole protection
Isolation by transformer
recommended