Restoring The Factory Settings With The Master Reset Button Via 3Rw5 Hmi High Feature - Siemens SIRIUS 3RW51 Equipment Manual

Soft starters and solid-state switching devices
Table of Contents

Advertisement

Result
The factory setting of the selected device or all devices is restored.
Note the effects of the factory settings described in Chapter Restore factory setting (Page 155).
10.4.2
Restoring the factory settings with the Master reset button via 3RW5 HMI High
Feature
Requirements
• 3RW5 HMI High Feature (accessory)
• Make sure that the motor is switched off and that you do not start the motor while restoring
the factory settings. To ensure the quickest and most fault-free restoration of the factory
setting, it is recommended that you disconnect the main voltage (operating voltage) at the
3RW51 soft starter.
• Free access to the Master RESET key of the 3RW5 HMI High Feature
Removing 3RW5 HMI High Feature (Page 40)
• 3RW5 HMI High Feature is connected to 3RW51 soft starter via the HMI connecting cable.
Procedure
1. Press the Master RESET button on the rear of the 3RW5 HMI High Feature.
The menu for restoring the factory setting appears on the display.
2. Select the desired menu item.
– 3RW5 soft starter
– Communication module
– 3RW5 HMI High Feature
– All devices
3. Confirm the menu item with "OK" key.
Result
The factory setting of the selected device or all devices is restored.
Note the effects of the factory settings described in Chapter Restore factory setting (Page 155).
SIRIUS 3RW51 Soft Starter
Equipment Manual, 09/2020, A5E37108631002A/RS-AC/003
Maintenance and servicing
10.4 Restore factory setting
157