3−18
DC Braking (DB) Settings
Normal DC braking performance⎯ The DC
braking feature can provide additional
stopping torque when compared to a normal
deceleration to a stop. DC braking is
particularly useful at low speeds when
normal deceleration torque is minimal. When
you enable DC braking, the inverter injects a
DC voltage into the motor windings during
deceleration below a frequency you can
specify (A052).
The braking power (A054) and duration (A055) can both be set. You can optionally
specify a wait time before DC braking (A053), during which the motor will free run.
DC Braking – Frequency Detection⎯ All above operations are done when the RUN
command (FW signal) turns OFF. But you can even set DC braking during Run by
setting
frequency comes down to the one you specified (A052) even the Run command is active.
External DB and Internal DC are invalid during the frequency detection mode.
FW
F-SET
A052
F-OUT
Example 1, above to the left shows the performance when giving the pulsing frequency
set point. In this case, when changing set point to 0, inverter immediately starts DB
because the set point becomes lower than the value specified in A052. And the DB
continues until the set point exceeds A052. And there will be no DC braking at next stop
because the FW is being OFF.
Example 2, above to the right shows the gradual change in frequency set point, for
example by analog input. In this case, there will be a DC braking period at start
because the frequency set point is lower than the value specified in A052.
More user manuals on
frequency detection
ON
DB
Ex.1) Step change in F-SET.
ManualsBase.com
+
0
-
at A051. In this case the DC brake operates when the output
FW
F-SET
A052
F-OUT
Ex.2) Analog change in F-SET.
Running
Free run
DC brake
A053
A055
ON
DB
DB
t
DB