PID ON/OFF and PID Clear
The PID loop function is useful for controlling motor speed to achieve constant flow,
pressure, temperature, etc. in many process applications. The PID Disable function
temporarily suspends PID loop execution via an intelligent input terminal. It overrides
the parameter A071 (PID Enable) to stop PID execution and return to normal motor
frequency output characteristics. the use of PID Disable on an intelligent input terminal
is optional. Of course, any use of the PID loop control requires setting PID Enable
function A071=01.
The PID Clear function forces the PID loop integrator sum = 0. So, when you turn ON
an intelligent input configured as [PIDC], the integrator sum is reset to zero. This is
useful when switching from manual control to PID loop control and the motor is
stopped.
CAUTION: Be careful not to turn PID Clear ON and reset the integrator sum when the
inverter is in Run Mode (output to motor is ON). Otherwise, this could cause the motor
to decelerate rapidly, resulting in a trip.
Option
Code
23
24
Valid for inputs:
Required settings
Notes:
• The use of [PID] and [PIDC] terminals are
optional. Use A071=01 if you want PID loop
control enabled all the time.
• Do not enable/disable PID control while the
motor is running (inverter is in Run Mode).
• Do not turn ON the [PIDC] input while the
motor is running (inverter is in Run Mode).
More user manuals on
Terminal
Function Name
Symbol
PID
PID Disable
PIDC
PID Clear
C001~C005
A071
ManualsBase.com
State
Description
ON
Disables PID loop execution
OFF
Allows PID loop execution
ON
Force the value of the integrator to zero
OFF
No change in PID loop execution
Example (default input configuration shown—see
page
3–49):
PIDC PID
5
4
See I/O specs on
page 4–6.