Hitachi X200-002SFE/NFU Instruction Manuals page 182

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

The alarm relay output can be configured in two main ways:
Be sure to use the relay configuration that is appropriate for your system design. Note
that the external circuits shown assume that a closed circuit = no alarm condition (so
that a broken wire also causes an alarm). However, some systems may require a closed
circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2]
from the ones shown.
During normal operation When an alarm occurs or
AL0
AL1
Power
supply
Power
ON
ON
OFF
More user manuals on
Trip/Power Loss Alarm – The alarm relay is configured as normally closed
(C036=1) by default, shown below (left). An external alarm circuit that detects
broken wiring also as an alarm connects to [AL0] and [AL1]. After powerup and
short delay (< 2 seconds), the relay energizes and the alarm circuit is OFF. Then,
either an inverter trip event or an inverter power loss will de-energize the relay
and open the alarm circuit
Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0),
shown below (right). An external alarm circuit that detects broken wiring also as
an alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only
when an inverter trip event occurs, opening the alarm circuit. However, in this
configuration, an inverter power loss does not open the alarm circuit.
N.C. contacts (C036=01)
when power is OFF
AL2
AL0
AL1
Power
Load
supply
Run Mode
AL0-AL1
Normal
Closed
Trip
Open
Open
ManualsBase.com
During normal operation
or when power is OFF
AL2
AL0
AL1
Power
Load
supply
AL0-AL2
Power
Run Mode
Open
ON
Closed
ON
Closed
OFF
N.O. contacts (C036=00)
When an alarm occurs
AL2
AL0
AL1
Power
Load
Load
supply
AL0-AL1
AL0-AL2
Normal
Open
Closed
Trip
Closed
Open
Open
Closed
4−43