4−28
It is possible for the inverter to retain the frequency set from the [UP] and [DWN]
terminals through a power loss. Parameter C101 enables/disables the memory. If
disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use
the [UDC] terminal to clear the memory and return to the original set output frequency.
Option
Code
27
28
29
Valid for inputs:
Required settings
Notes:
• This feature is available only when the frequency
command source is programmed for operator
control. Confirm A001 is set to 02.
• This function is not available when [JG] is in use.
• The range of output frequency is 0 Hz to the value
in A004 (maximum frequency setting).
• The minimum ON time of [UP] and [DWN] is 50 ms.
• This setting modifies the inverter speed from using F001 output frequency setting as a starting point.
More user manuals on
Terminal
Function Name
Symbol
UP
Remote Control UP
Function (motorized
speed pot.)
DWN
Remote Control
DOWN Function
(motorized speed pot.)
UDC
Remote Control Data
Clear
C001~C005
A001 = 02
ManualsBase.com
State
Description
ON
Accelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Decelerates (increases output frequency) motor
from current frequency
OFF
Output to motor operates normally
ON
Clears the Up/Down frequency memory
OFF
No effect on Up/Down memory
Example (default input configuration shown—see
page
3–49):
DWN
5
4
See I/O specs on
page 4–6.
UP
L PCS P24
3
2
1