DIP Switch Introduction
The inverter has internal DIP switches, located at the middle of the logic connectors as
shown below. This selection provides an introduction, and refers you to other chapter
that discuss the DIP switch in depth.
More user manuals on
SW7
The 485/OPE (RS485/Operator) DIP switch configures the
inverter's RS485 serial port. You can use either the inverter's
485
integrated keypad or the OPE (OPE SR-mini) connected via a
cable to the serial port. In this case the SW7 should be set OPE
(default
communication requires the "485" setting. See
OPE
Inverter to ModBus" on page B-3
SW8
The SW8 is for the emergency signal input. If you turn this DIP
ON
switch ON, the inverter is ready to receive emergency signal
from the dedicated terminal #3. Inverter shuts off the output by
means of pure hardware when a signal is given to the terminal.
OFF
It complies to EN954-1, category 3. Each signals related to this
emergency input must be in accordance with the norm.
Additionally, the logic input terminal assign will be changed
automatically if the SW8 is made ON. See
4-32
ManualsBase.com
SW7
485
OPE
set).
Inverter
control
for more details.
SW8
ON
OFF
via
a
ModBus
network
"Connecting the
for more details.
"Safe Stop" on page