Hitachi X200-002SFE/NFU Instruction Manuals page 125

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

Input Function Summary Table – This table shows all thirty-one intelligent input
functions at a glance. Detailed description of these functions, related parameters and
settings, and example wiring diagrams are in
page
Option
Code
00
01
02
03
04
05
06
07
08
09
11
12
13
15
16
18
More user manuals on
4-8.
Input Function Summary Table
Terminal
Function Name
Symbol
FW
FORWARD Run/Stop
RV
Reverse Run/Stop
CF1 *1
Multi-speed Select,
Bit 0 (LSB)
CF2
Multi-speed Select,
Bit 1
CF3
Multi-speed Select,
Bit 2
CF4
Multi-speed Select,
Bit 3 (MSB)
JG
jogging
DB
External DC braking
SET
Set (select) 2nd Motor
Data
2CH
2-stage Acceleration
and Deceleration
FRS
Free-run Stop
EXT
External Trip
USP
Unattended Start
Protection
SFT
Software Lock
AT
Analog Input
Voltage/Current Select
RS
Reset Inverter
ManualsBase.com
"Using Intelligent Input Terminals" on
Description
ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
ON
Inverter is in Run Mode, output to motor runs
at jog parameter frequency
OFF
Inverter is in Stop Mode
ON
DC braking will be applied during deceleration
OFF
DC braking will not be applied
ON
The inverter uses 2nd motor parameters for
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters
for generating frequency output to motor
ON
Frequency output uses 2nd-stage acceleration
and deceleration values
OFF
Frequency output uses standard acceleration
and deceleration values
ON
Causes output to turn OFF, allowing motor to
free run (coast) to stop
OFF
Output
operates
deceleration stop motor
ON
When assigned input transitions OFF to ON,
inverter latches trip event and displays E12
OFF
No trip event for ON to OFF, any recorded trip
events remain in history until reset
ON
On powerup, the inverter will not resume a Run
command (mostly used in the US)
OFF
On powerup, the inverter will resume a Run
command that was active before power loss
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
ON
Refer to
"Analog Input Settings" on page
OFF
ON
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
OFF
Normal power-ON operation
3−51