Hitachi X200-002SFE/NFU Instruction Manuals page 261

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

B−34
Func.
Code
B086
Frequency scaling
conversion factor
B087
STOP key enable
B088
Restart mode after
FRS
B089
Monitor display
select for networked
inverter
B091
Stop mode selection R/W Select how the inverter stops the motor,
B092
Cooling fan control
B130
Over-voltage
LADSTOP enable
B131
Over-voltage
LADSTOP level
More user manuals on
Name
R/W
R/W Specify a constant to scale the displayed
frequency for D007 monitor, range is 0.1
to 99.9
R/W Select whether the STOP key on the
keypad is enabled,
two option codes:
00...Enabled
01...Disabled
R/W Selects how the inverter resumes
operation with free-run stop (FRS) is
cancelled, two options:
00...Restart from 0Hz
01...Restart from frequency detected
R/W Selects the parameter displayed on the
keypad display when the inverter is
networked, 7 options:
01...Output frequency monitor
02...Output current monitor
03...Rotation direction monitor
04...Process variable (PV), PID feedback
05...Intelligent input terminal status
06...Intelligent output terminal status
07...Scaled output frequency monitor
two option codes:
00...DEC (decelerate to stop)
01...FRS (free run to stop)
R/W Selects when the fan is ON per inverter
operation, three options:
00...Fan is always ON
01...Fan is ON during run, OFF during
02...Fan is temperature controlled
R/W Pauses deceleration ramp when DC bus
voltage rises above threshold level, in
order to avoid over-voltage trip.
Two option codes:
00...Disable
01...Enable
R/W Sets the threshold level for over-voltage
LADSTOP. When the DC bus voltage is
above the threshold value, the inverter
stops deceleration until the DC bus
voltage is less than the threshold setting
again. Two voltage ranges with 1V
resolution:
330 to 395V (200V class)
660 to 790V (400V class)
ManualsBase.com
List of Holding Registers
Description
from real speed of motor (frequency
matching)
monitor
stop (5 min. delay from ON to OFF)
Network Data
Reg.
Range
Res.
10D5h
1 to 999
0.1
10D6h
0, 1
10D7h
0, 1
10D8h
1 to 7
10DAh
0, 1
10DBh
0, 1, 2
10F5h
0, 1
10F6h 330 to 395,
1 V
660 to 790