Hitachi X200-002SFE/NFU Instruction Manuals page 218

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

IGBT Test Method
The following procedure will check the inverter transistors (IGBTs) and diodes:
1. Disconnect input power to terminals [R, S, and T] and motor terminals [U, V, and W].
2. Disconnect any wires from terminals [+] and [–] for regenerative braking.
3. Use a Digital Volt Meter (DVM) and set it for 1Ω resistance range. You can check the
Table Legend Almost infinite resistance: ≅ ∞ Ω Almost zero resistance: ≅ 0 Ω
Part
NOTE: The resistance values for the diodes or the transistors will not be exactly the
same, but they will be close. If you find a significance difference, a problem may exist.
NOTE: Before measuring the voltage between [+] and [–] with the DC current range,
confirm that the smoothing capacitor is discharged fully, then execute the tests.
More user manuals on
status of the charging state of terminals [R, S, T, U, V, W, +, and –] of the inverter
and the probe of the DVM by measuring the charging state.
DVM
Measured
Value
+
D1
[R] [+1]
≅ ∞ Ω
[+1] [R]
≅ 0 Ω
D2
[S] [+1]
≅ ∞ Ω
[+1] [S]
≅ 0 Ω
D3
[T] [+1]
≅ ∞ Ω
[+1] [T]
≅ 0 Ω
D4
[R]
[–]
≅ 0 Ω
[–]
[R]
≅ ∞ Ω
ManualsBase.com
Part
DVM
Measured
Part
Value
+
D5
[S] [–]
≅ 0 Ω
TR3
[–] [S]
≅ ∞ Ω
D6
[T] [–]
≅ 0 Ω
TR4
[–] [T]
≅ ∞ Ω
TR1
[U] [+]
≅ ∞ Ω
TR5
[+] [U]
≅ 0 Ω
TR2
[V] [+]
≅ ∞ Ω
TR6
[+] [V]
≅ 0 Ω
DVM
Measured
Value
+
[W] [+]
≅ ∞ Ω
[+] [W]
≅ 0 Ω
[U] [–]
≅ 0 Ω
[–] [U]
≅ ∞ Ω
[V] [–]
≅ 0 Ω
[–] [V]
≅ ∞ Ω
[W] [–]
≅ 0 Ω
[–] [W]
≅ ∞ Ω
6−15