3−46
DC Bus AVR for deceleration Settings
This function is to achieve stable DC bus voltage in case of deceleration. DC bus voltage
raises due to regeneration during deceleration. When this function is activated
(B133=01), inverter controls the deceleration time so that the DC bus voltage not to go
up to the overvoltage trip level, and leads to the tripless operation during deceleration.
Please note that the actual deceleration time may be longer in this case.
Func.
Code
B055
B056
B057
B133
B134
More user manuals on
DC bus voltage
Freq
Normal
operation
"B" Function
Name /
SRW Display
DC bus AVR for decel.
P-gain
VpnP
0000.2s
DC bus AVR for decel.
I-time
VpnI
0000.2s
DC bus AVR for decel.
D-time
VpnD
0000.2s
DC bus AVR selection
Vpn AVR
OFF
Threshold voltage of DC bus
AVR setting
Vpn LVL
00380V
ManualsBase.com
Threshold voltage to start DC bus AVR (B134)
t
t
DC bus AVR
Description
Proportional gain adjustment for
DC bus AVR function. Range is:
0.2 to 5.0
Integration time adjustment for
DC bus AVR function. Range is:
0.0 to 150.0
Derivative time adjustment for
DC bus AVR function. Range is:
0.0 to 100.0
00...Disabled
01...Enabled
Setting of threshold voltage of
DC bus voltage to start DC bus
AVR function. Range is:
200V class...330 to 395
400V class...660 to 790
Run
Defaults
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.2
0.2
0.2
0.2
sec
0.0
0.0
sec
00
00
380
380
V
/760
/760