Overload Restriction
If the inverter's output current exceeds a
preset current level you specify during
acceleration or constant speed, the overload
restriction feature automatically reduces the
output frequency to restrict the overload.
This feature does not generate an alarm or
trip event. You can instruct the inverter to
apply
constant
currents for acceleration. Or, you may use
the same threshold for both acceleration and
constant speed.
When the inverter detects an overload, it
must decelerate the motor to reduce the
current until it s less than the threshold. You
can choose the rate of deceleration that the
inverter uses to lower the output current.
Func.
Code
B021
B221
B022
B222
B023
B223
B028
B228
Frequency Pull-in Restart
See "
More user manuals on
overload
restriction
speed,
thus
"B" Function
Name /
SRW Display
Overload restriction
operation mode
OL Mode
ON
Overload restriction
operation mode, 2nd motor
2OL Mode
ON
Overload restriction level
setting
OL LVL
002.40A
Overload restriction level
setting, 2nd motor
2OL LVL
002.40A
Deceleration rate at overload
restriction
OL Cnst
0001.0s
Deceleration rate at overload
restriction, 2nd motor
2OL Cnst
0001.0s
Source of overload restriction
selection
OL L_SLCT
PARAM
Source of overload restriction
selection, 2nd motor
2OL L_SLCT
PARAM
Restart Mode Configuration " (B088) section on page
ManualsBase.com
Motor
current
B022
only
during
allowing
higher
Output
frequency
Description
Select the operation mode during
overload conditions, three
options, option codes:
00...Disabled
01...Enabled for acceleration and
constant speed
02...Enabled for constant speed
only
Sets the level for overload
restriction, between 20% and
150% of the rated current of the
inverter, setting resolution is 1%
of rated current
Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution 0.1
Two option codes:
00...set value of B022
01...[O] input
Two option codes:
00...set value of B222
01...[O] input
Restriction area
0
0
B022
Run
Defaults
Mode
-FE
-FU
Edit
(EU)
(USA)
01
01
01
01
Rated
current
x 1.5
Rated
current
x 1.5
1.0
30.0
1.0
30.0
00
00
00
00
3-42.
3−35
t
t
Units
A
A
sec.
sec.