F" Group: Main Profile Parameters - Hitachi X200-002SFE/NFU Instruction Manuals

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

"F" Group: Main Profile Parameters

The basic frequency (speed) profile is
defined by parameters contained in the "F"
Group as shown to the right. The set
running frequency is in Hz, but acceleration
and deceleration are specified in the time
duration of the ramp (from zero to
maximum frequency, or from maximum
frequency to zero). The motor direction
parameter determines whether the keypad
Run key produces a FWD or REV command.
This parameter does not affect the intelligent terminal [FW] and [REV] functions,
which you configure separately.
Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the
main profile. Accel and decel values for an alternative profile are specified by using
parameters Ax92 through Ax93. The motor direction selection (F004) determines the
direction of rotation as commanded only from the keypad. This setting applies to any
motor profile (1st or 2nd) in use at t particular time.
Func.
Code
F001
F002
F202
F003
F203
F004
More user manuals on
"D" Function
Name /
SRW Display
Output frequency setting
VR
0000.0Hz
Acceleration (1) time setting
ACC 1
010.00s
Acceleration (1) time setting,
2nd motor
2ACC 1
010.00s
Deceleration (1) time setting
DEC 1
010.00s
Deceleration (1) time setting,
2nd motor
2DEC 1
010.00s
Cumulative power-on time
monitor
DIG-RUN
FWD
ManualsBase.com
Output
frequency
F001
0
Description
Standard default target
frequency that determines
constant motor speed, range is
0.0 / start frequency to 400 Hz
Standard default acceleration,
range is 0.01 to 3000 sec.
Standard default acceleration,
2nd motor
range is 0.01 to 3000 sec.
Standard default deceleration,
range is 0.01 to 3000 sec.
Standard default deceleration,
2nd motor
range is 0.01 to 3000 sec.
Two options; select codes:
00 ...Forward
01 ...Reverse
F002
F003
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.0
0.0
Hz
10.0
10.0
sec.
10.0
10.0
sec.
10.0
10.0
sec.
10.0
10.0
sec.
00
00
3−9
t

Advertisement

Table of Contents
loading

Table of Contents