Output Function Summary Table – This table shows all twelve functions for the logical
outputs (terminals [11] and [AL]) at a glance. Detailed descriptions of these functions,
related parameters and settings, and example wiring diagrams are in
Output Terminals" on page
Option
Code
00
01
02
03
04
05
06
07
08
09
10
43
More user manuals on
4-34.
Output Function Summary Table
Terminal
Function Name
Symbol
RUN
Run Signal
FA1
Frequency Arrival Type
1–Constant Speed
FA2
Frequency Arrival Type
2–Over frequency
OL
Overload Advance
Notice Signal
OD
Output Deviation for
PID Control
AL
Alarm Signal
Dc
Analog Input
Disconnect Detect
FBV
PID Second Stage
Output
NDc
Network Detection
Signal
LOG
Logic Output Function
ODc
Communication option
error
LOC
Low load detection
ManualsBase.com
Description
ON
When the inverter is in Run Mode
OFF
When the inverter is in Stop Mode
ON
When output to motor is at the set frequency
OFF
When output to motor is OFF, or in any
acceleration or deceleration ramp
ON
When output to motor is at or above the set
frequency, even if in accel. or decel rams
OFF
When output to motor is OFF, or at a level
below the set frequency
ON
When output current is more than the set
threshold for the overload signal
OFF
When output current is less than the set
threshold for the deviation signal
ON
When PID error is more than the set threshold
for the deviation signal
OFF
When PID error is less than the set threshold
for the deviation signal
ON
When an alarm signal has occurred and has not
been cleared
OFF
When no alarm has occurred since the last
cleaning of alarm(s)
ON
When the [O] input value < B082 setting (signal
loss detected), or the [OI] input current < 4mA
OFF
When no signal loss is detected
ON
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)
OFF
Transitions to OFF when the PID Process
Variable (PV) exceeds the PID High Limit
(C052), and transitions to OFF when the
inverter goes from Run Mode to Stop Mode
ON
When the communications watchdog timer
(period specified by C077) has time out
OFF
When the communications watchdog timer is
satisfied by regular communications activity
ON
When the Boolean operation specified by C143
has a logical "1" result
OFF
When the Boolean operation specified by C143
has a logical "0" result
ON
No communication between communication
option is detected during a time set in P044
OFF
Communication is normal
ON
Motor current is less than the set value of C039
OFF
Motor current is not less than the set value of
C039
3−55