Force Terminal Mode; Inverter Ready - Hitachi X200-002SFE/NFU Instruction Manuals

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

Force Terminal Mode

The purpose of this intelligent input is to allow a device to force the inverter to allow
control of the following two parameters via the control terminals:
Some applications will require one or both settings above to use a source other than the
terminals. You may prefer to normally use the inverter's keypad and potentiometer, or
to use the ModBus network for control, for example. However, an external device can
turn ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency
source and Run command) via control terminals. When the [F-TM] input is OFF, then
the inverter uses the regular sources specified by A001 and A002 again.
Option
Code
51
Valid for inputs:
Required settings
Notes:
• When changing the [F-TM] state during Run
Mode (inverter is driving the motor), the
inverter will stop the motor before the new [F-
TM] state takes effect.

Inverter Ready

The purpose of this intelligent input is to make inverter ready to start the motor
immediately when the RUN command is given. When the RDY input is active, motor
output terminal is active even if there is no RUN command.
Option
Code
52
Valid for inputs:
Required settings
Notes:
HIGH VOLTAGE: When set RDY function ON, there will be a voltage appear at
motor output terminals U, V and W even if the motor is in stop mode. So never touch
the inverter power terminal even the motor is not running.
More user manuals on
• A001 - Frequency source setting (01 = control terminals [FW] and [RV]
• A002 - Run command source setting (01 = control terminals [O] or [OI]
Terminal
Function Name
Symbol
F-TM
Force Terminal
Mode
C001~C005
A001, A002
Terminal
Function Name
Symbol
RDY
Inverter Ready
C001~C005
A001, A002
ManualsBase.com
State
Description
ON
Forces A001=01 (frequency source setting =
control terminal), and A002=01(Run command
source setting = control terminal)
OFF
Inverter applies the user setting for A001 and
A002 normally
Example (default input configuration shown—see
page
3–49):
5
4
See I/O specs on
page 4–6.
State
Description
ON
Inverter is ready to act immediately when the
RUN command is given.
OFF
Inverter performs normal start when the RUN
command is given.
Example (default input configuration shown—see
page
3–49):
5
4
See I/O specs on
page 4–6.
4−31
F-TM
L PCS P24
3
2
1
RDY
L PCS P24
3
2
1