The data set in the response is as follows:
When the Read Holding Register command cannot be executed normally, refer to the
exception response.
Write in Coil [05h]:
This function writes data in a single coil. Coil status changes are as follows:
An example follows (note that to command the inverter, set A002=03):
• Sending a RUN command to an inverter having slave address "8"
• This example writes in coil number "1."
Query:
Note 1:
Note 2:
When writing in a selected coil fails, see the exception response.
More user manuals on
Response Buffer
Register Number
12+0 (high
order)
Register Data
Trip data
Trip factor (E03)
Response Buffer
Register Number
12+3 (high
order)
Register Data
00h
Trip data
Data
Change data (high order)
Change data (low order)
No.
Field Name
1
Slave address *1
2
Function code
3
Coil start address *2
(high order)
4
Coil start address *2
(low order)
5
Change data
(high order)
6
Change data
(low order)
7
CRC-16 (high order)
8
CRC-16 (low order)
No response is made for a broadcasting query.
The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31
are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1
less than the Coil Number.
ManualsBase.com
4-5
12+0
12+1
(low
(high
order)
order)
0003h
00h
Not used
10-11
12-13
12+3
12+4
(low
(high
order)
order)
00h
001Eh
Not used
Output current (3.0A)
Coil Status
OFF to ON
FFh
00h
Response:
Example
No.
Field Name
(Hex)
08
1
Slave address
05
2
Function code
00
3
Coil start address *2
(high order)
00
4
Coil start address *2
(low order)
FF
5
Change data
(high order)
00
6
Change data
(low order)
8C
7
CRC-16 (high order)
A3
8
CRC-16 (low order)
6-7
8-9
12+1 (low
12+2
order)
(high
order)
00h
0063h
Frequency (9.9Hz)
14-15
12+4 (low
12+5
order)
(high
order)
011Ch
DC-bus voltage (284V)
ON to OFF
00h
00h
Example
(Hex)
08
05
00
00
FF
00
8C
A3
12+2 (low
order)
12+5 (low