Hitachi X200-002SFE/NFU Instruction Manuals page 69

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

2−30
If the Potentiometer Enable LED is OFF, follow these steps below.
Select the Keypad for RUN Command – To RUN
command causes the inverter to accelerate the motor
to the selected speed. The Run command can arrive
from various sources, including the control terminals,
the Run key on the keypad or the network. In the
figure to the right, notice the Run Key Enable LED,
just above the Run key. If the LED is ON, the Run
key is already selected as the source, and you may
skip this step. Note that the default setting depends
on the country.
If the Potentiometer Enable LED is OFF, follow these steps below (the table resumes
action from the end of the previous table).
NOTE: After completing the steps above, the Run Key Enable LED will be ON. This
does not mean the motor is trying to run; it means that the RUN key is now enabled.
DO NOT press the RUN key at this time – complete the parameter setup first.
More user manuals on
Action
(Starting point)
Press the
key.
FUNC
Press the
FUNC
key again.
Press the
key.
2
STR
Press the
key.
Action
(Starting point)
Press the
key once.
1
FUNC
Press the
key.
Press the
key.
1
STR
Press the
key.
ManualsBase.com
Display
Func./Parameter
A- - -
"A" Group selected
A001
Speed command source setting
00 = Keypad potentiometer
01 = Control terminals
01
02 = Function F001 setting
03 = ModBus network
04 = Calculate function output
00
00 = Potentiometer (selected)
Store parameter, returns to "A"
A001
Group list
Run Key Enable LED
RUN
FUNC
Display
Func./Parameter
A001
Speed command source setting
A002
Run command source setting
01 = Control terminals
01
02 = Run key on keypad
03 = ModBus network
02
02 = Run key on keypad (selected)
Store parameter, returns to "A"
A002
Group list
POWER
Hz
ALARM
A
STOP
RUN
RESET
PRG
STR
2
1