3−64
Output Signal ON/OFF Delay Function – Intelligent outputs including terminals [11]
and the output relay, have configurable signal transition delays. Each output can delay
either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are
variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor
inverter output signals to meet timing requirements of certain external devices.
Func.
Code
C144
C145
C148
C149
NOTE: If you are using the output terminal OFF delay feature (any of C145, C149 > 0.0
sec.), the [RS] (reset) terminal affects the ON-to-OFF transition slightly. Normally (with
using OFF delays), the [RS] input causes the motor output and the logic outputs to turn
OFF together, immediately. However, when any output uses an OFF delay, then after
the [RS] input turns ON, that output will remain ON for an additional 1 sec. period
(approximate) before turning OFF.
More user manuals on
"C" Function
Name /
SRW Display
Terminal [11] ON delay
DLAY 11
000.0s
Terminal [11] OFF delay
HOLD 11
000.0s
Output relay ON delay
DLAY RY
000.0s
Output relay OFF delay
HOLD RY
000.0s
ManualsBase.com
Description
Range is 0.0 to 100.0 sec.
Range is 0.0 to 100.0 sec.
Range is 0.0 to 100.0 sec.
Range is 0.0 to 100.0 sec.
Defaults
Run
Mode
-FE
-FU
Units
Edit
(EU)
(USA)
0.0
0.0
sec.
0.0
0.0
sec.
0.0
0.0
sec.
0.0
0.0
sec.