3−16
Torque Control Algorithms
The inverter generates the motor output according
to the V/f algorithm selected. Parameter A044
selects the inverter algorithm for generating the
frequency output, as shown in the diagram to the
right (A244 for 2nd motor). The factory default is
00 (constant torque).
Review the following description to help you choose the best torque control algorithm for
your application.
The built-in V/f curve are oriented toward developing constant torque or variable torque
characteristics (see graphs below). You can select either constant torque or reduced
torque V/f control.
Constant and Variable (Reduced) Torque – The
graph at right shows the constant torque
characteristic from 0Hz to the base frequency
A003. The voltage remains constant for output
frequencies higher than the base frequency. The
graph below (left) shows the general variable
(reduced) torque curve. The range from 0Hz to
the base frequency is the variable characteristic.
The graph above (right) shows the variable (reduced) torque curve, having constant
torque from 0Hz to 10% of the base frequency. This helps to achieve higher torque at low
speed even with reduced torque curve.
Manual Torque Boost – The Constant
and
feature an adjustable
curve. When the motor load has a lot of
inertia or starting friction, you may
need to increase the low frequency
starting
boosting the voltage above the normal
V/f ratio (shown at right). The function
attempts to compensate for voltage
drop in the motor primary winding in
the low speed range.
The boost is applied from zero to 1/2 the base frequency. You set the breakpoint of the
boost (point A on the graph) by using parameters A042 and A043. The manual boost is
calculated as an addition to the standard V/f curve.
More user manuals on
V
Variable torque
A044 = 01
100%
0
Base
freq.
Variable
Torque
torque boost
torque
characteristics
ManualsBase.com
Inverter Torque Control Algorithms
Variable freq. control,
Variable freq. control,
Variable freq. control,
V
100%
V
100%
Hz
Max.
freq.
algorithms
A042 = 5(%)
100%
5% boot of
the base
by
frequency
0
00
constant torque
01
reduced torque
06
reduced torque1
Constant torque
A044 = 00
0
Base
freq.
Variable torque
A044 = 06
0
10% Base
Base
freq.
freq.
V
A
1.8Hz
30Hz
fbase = 60Hz
A043 = 3(%)
A044
Output
Hz
Max.
freq.
Hz
Max.
freq.
Hz