Force Operation from Digital Operator
This function permits a digital operator interface to override the following two settings
in the inverter:
When using the [OPE] terminal input, typically A001 and A002 are configured for
sources other than the digital operator interface for the output frequency and Run
command sources, respectively. When the [OPE] input is ON, then user has immediate
command of the inverter, to start or stop the motor and to set the speed.
Option
Code
31
Valid for inputs:
Required settings
Notes:
• When changing the [OPE] state during Run
Mode (inverter is driving the motor), the
inverter will stop the motor before the new
[OPE] state takes effect.
• If the [OPE] input turns ON and the digital
operator gives a Run command while the
inverter is already running, the inverter stops
the motor. Then the digital operator can control
the motor.
More user manuals on
A001 - Frequency source setting
A002 - Run command source setting
Terminal
Function Name
Symbol
OPE
Force Operation
from Digital
Operator
C001~C005
A001 (set not equal to 00)
A002 (set not equal to 02)
ManualsBase.com
State
Description
ON
Forces the operator interface to override:
A001 - Frequency Source Setting, and A002 - Run
Command Source Setting
OFF
Parameters A001 and A002 are in effect again,
for the frequency source and the Run command
source, respectively
Example (default input configuration shown—see
page
3–49):
OPE
5
4
See I/O specs on
page 4–6.
4−29
L PCS P24
3
2
1