Add Frequency Enable

The inverter can add or subtract an offset value to the output frequency setting which is
specified by A001 (will work with any of the five possible sources). The ADD Frequency
is a value you can store in parameter A145. The ADD Frequency is summed with or
subtracted from the output frequency setting only when the [ADD] terminal is ON.
Function A146 selects whether to add or subtract. By configuring an intelligent input as
the [ADD] terminal, your application can selectively apply the fixed value in A145 to
offset (positively or negatively) the inverter output frequency in real time.
Option
Code
50
Valid for inputs:
Required settings
Notes:
• A001 may specify any source; the Add
Frequency will be added to or subtracted from
that value to yield output frequency value.
More user manuals on
Keypad potentiometer
Control terminal
Function F001 setting
ModBus network input
Calculate function output
A145 ADD frequency
Intelligent input
Terminal
Function Name
Symbol
ADD
ADD Frequency
Enable
C001~C005
A001, A145, A146
ManualsBase.com
Frequency source setting
A001
+
Σ
+/-
[ADD]
State
Description
ON
Applies the A145 Add Frequency value to the
output frequency
OFF
Does not apply the Add frequency. The output
frequency retains its normal value
Example (default input configuration shown—see
page
3–49):
ADD
5
4
3
See I/O specs on
page 4–6.
Output frequency setting
A146
ADD direction select
L PCS P24
2
1