Wiring - Warnings for Electrical Practice and Wire Specifications
WARNING: "USE 60/75°C Cu wire only" or equivalent.
WARNING: "Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 240V maximum." For models with suffix S or L.
CAUTION: "Suitable for use on a circuit capable of delivering not more than 5,000 rms
symmetrical amperes, 480V maximum." For models with suffix H.
HIGH VOLTAGE: Be sure to ground the unit. Otherwise, there is a danger of electric
shock and/or fire.
HIGH VOLTAGE: Wiring work shall be carried out only by qualified personnel.
Otherwise, there is a danger of electric shock and/or fire.
HIGH VOLTAGE: Implement wiring after checking that the power supply is OFF.
Otherwise, you may incur electric shock and/or fire.
HIGH VOLTAGE: Do not connect wiring to an inverter operate an inverter that is not
mounted according to the instructions given in this manual.
Otherwise, there is a danger of electric shock and/or injury to personnel.
WARNING: Make sure the input power to the inverter is OFF. If the drive has been
powered, leave it OFF for five minutes before continuing.
CAUTION: Power terminal assignment is different compared to old models such as
L100, L200 series, etc,. Pay attention when wiring the power cable.