Data:
• A function command is set here.
• The data format used in the X200 series is corresponding to the Modbus data format
Coil
Holding Register
Function code:
Specify a function you want to make the inverter execute. Function codes available to
the X200 series are listed below.
Function Code
Error check:
Modbus-RTU uses CRC (Cyclic Redundancy Check) for error checking.
• The CRC code is 16-bit data that is generated for 8-bit blocks of arbitrary length.
• The CRC code is generated by a generator polynomial CRC-16 (X16+ X15+ X2+ 1).
Header and trailer (silent interval):
Latency is the time between the reception of a query from the master and transmission
of a response from the inverter.
• 3.5 characters (24 bits) are always required for latency time. If the latency time
• The actual transmission latency time is the sum of silent interval (3.5 characters
More user manuals on
below.
Name of Data
Binary data that can be referenced and changed ( 1 bit long)
16-bit data that can be referenced and changed
Function
0 1 h
Read Coil Status
0 3 h
Read Holding Resistor
0 5 h
Write in Coil
0 6 h
Write in Holding Register
0 8 h
Loopback Test
0 F h
Write in Coils
1 0 h
Write in Registers
shorter than 3.5 characters, the inverter returns no response.
long) + C078 (transmission latency time).
ManualsBase.com
Description
Maximum data size
Maximum number of
(bytes available
data elements available
per message)
per message
4
32 coils (in bits)
4
4 registers (in bytes)
1
1 coil (in bits)
1
1 register (in bytes)
4
32 coils (in bits)
4
4 registers (in bytes)