Hitachi X200-002SFE/NFU Instruction Manuals page 144

X200 series. single-phase input 200v class. three-phase input 200v class. three-phase input 400v class.
Table of Contents

Advertisement

Example Wiring Diagram
The schematic diagram below provides a general example of logic connector wiring, in
addition to basic power and motor wiring converted in Chapter 2. The goal of this
chapter is to help you determine the proper connections for the various terminals shown
below for your application needs.
Power source,
3-phase or 1-
phase, per
inverter model
NOTE: For the wiring
of intelligent I/O and
analog inputs, be sure
to use twisted pair /
shielded cable. Attach
the shielded wire for
each signal to its
respective common
terminal at the inverter
end only.
Thermistor
More user manuals on
Breaker,
MCCB or GFI
R
(L1)
S
(L2)
T
N(L3)
Intelligent inputs,
5 terminals
P24
Forward
Reverse
PLC
GND for logic inputs
Meter
AM
Analog reference
H
0~10VDC
O
4~20mA
OI
GND for analog signals
ManualsBase.com
X200
24V
+ -
1
2
Input
circuits
3
4
[5] configurable as
5
discrete input or
thermistor input
L
Output circuit
L
U
(T1)
Motor
V
(T2)
W
(T3)
PD/+1
DC reactor
(optional)
P/+
Braking
unit
N/-
(optional)
AL1
Relay contacts,
type 1 Form C
AL0
AL2
Open collector output
Freq. arrival signal
11
Load
+
-
CM2
GND for logic outputs
4−5

Advertisement

Table of Contents
loading

Table of Contents