Signal Ratings
Detailed ratings are in "Control Logic Signal Specifications" on page 4-6.
Signal / Contact
Built-in power for inputs
Discrete logic inputs
Discrete logic outputs
Analog output
Analog input, current
Analog input, voltage
+10V analog reference
Alarm relay contacts
More user manuals on
24VDC, 30mA maximum
27VDC maximum
50mA maximum ON state current, 27 VDC maximum OFF state voltage
0 to 10VDC, 1mA
4 to 19.6 mA range, 20mA nominal
0 to 9.8 VDC range, 10VDC nominal, input impedance 10kΩ
10VDC nominal, 10mA maximum
250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min
30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.)
5 VDC, 100mA min.