1−14
Inverter Output to the Motor
3-phase AC motor
The AC motor must be connected only to the inverter's
output terminals. The output terminals are uniquely
U/T1
labeled (to differentiate them from the input terminals)
with the designations U/T1, V/T2, and W/T3. this
corresponds to typical motor lead connection designations
T1, T2, and T3. It is not often necessary to connect a
particular motor lead
for a
new application.
The
consequence of swapping any two of the three connections is
V/T2
the reversal of the motor direction. In applications where
W/T3
reversed rotation could cause equipment damage or
Earth GND
personnel injury, be sure to verify direction of rotation
before attempting full-speed operation.
For safety to personnel, you must connect the motor chassis ground to the ground
connection at the bottom of the inverter housing.
Notice the three connections to the motor do not include one marked "Neutral" or
"Return". The motor represents a balanced "Y" impedance of the inverter, so there is no
need for a separate return. In other words, each of the three "Hot" connections serves
also as a return for the other connections of their phase relationship.
The Hitachi inverter is a rugged and reliable device. The intention is for the inverter to
assure the role of controlling power to the motor during all normal operations. Therefore,
while the motor is
this manual instruct you not to switch off power to the inverter
running
(unless it is an emergency stop). Also, do not install or use disconnect switches
in the wiring from the inverter to the motor (except thermal disconnect). Of course,
safety-related devices such as fuses must be in the design to break power during a
malfunction, as required by NEC and local codes.