C Group: Intelligent Terminal Functions - Hitachi SJ700 Series Manual

Variable frequency drive
Hide thumbs Also See for SJ700 Series:
Table of Contents

Advertisement

Code
Function Name
b112
Free-setting V/f frequency (7)
b113
Free-setting V/f voltage (7)
b120
Brake control enable
b121
Brake wait time for release
b122
Brake wait time for acceleration
b123
Brake wait time for stopping
b124
Brake wait time for confirmation
b125
Brake release frequency setting
b126
Brake release current setting
b127
Braking frequency
b130
Overvoltage suppression enable
b131
Overvoltage suppression level
Acceleration and deceleration rate
b132
at overvoltage suppression
b133
Overvoltage suppression propotional gain
b134
Overvoltage suppression Integral time
(*1) 4000HF:0.0 to 120.0(Hz) (*2)4000HF:0.00 to 99.99, 100.0 to 120.0(Hz)
●C GROUP: INTELLIGENT TERMINAL FUNCTIONS
Code
Function Name
C001
Terminal [1] function (*1)
C002
Terminal [2] function
C003
Terminal [3] function (*1)
C004
Terminal [4] function
C005
Terminal [5] function
C006
Terminal [6] function
C007
Terminal [7] function
C008
Terminal [8] function
C011
Terminal (1) active state
C012
Terminal (2) active state
C013
Terminal (3) active state
C014
Terminal (4) active state
C015
Terminal (5) active state
C016
Terminal (6) active state
C017
Terminal (7) active state
C018
Terminal (8) active state
C019
Terminal FW active state
Terminal (11) function
C021
C022
Terminal (12) function
Terminal (13) function
C023
C024
Terminal (14) function
Terminal (15) function
C025
C026
Alarm relay terminal function
C027
FM signal selection
C028
AM signal selection
C029
AMI signal selection
(*1) When the emergency stop function is enabled (SW1 = ON), "18" (RS) and "64" (EMR) are forcibly written to parameters "C001" and "C003",
respectively. (You cannot arbitrarily write "64" to "C001".) If the SW1 signal is turned off and then turned on, "no" (no assignment) is set in parameter "C003".
(*2) L700 series: The function is not provided. (*3)1850HF,2200HF,3150HF and 4000HF:The function is not provided.
Monitored data or setting
0.0 to 400.0 (Hz) (*1)
0.0 to 800.0 (V)
00 (disabling), 01 (enabling)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 5.00 (s)
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
0.0 to 2.00 x "rated current"
0.00 to 99.99, 100.0 to 400.0 (Hz) (*2)
00 (disabling the restraint), 01 (decelerating and stagnating), 02 (enabling acceleration)
330 to 390 (V) (200 V class model), 660 to 780 (V) (400 V class model)
0.10 to 30.00 (s)
0.00 to 2.55
0.000 to 9.999 / 10.00 to 63.53 (s)
Monitored data or setting
01 (RV: Reverse RUN), 02 (CF1: Multispeed 1 setting), 03 (CF2: Multispeed 2 setting),
04 (CF3: Multispeed 3 setting), 05 (CF4: Multispeed 4 setting), 06 (JG: Jogging), 07 (DB:
external DC braking), 08 (SET: Set 2nd motor data), 09 (2CH: 2-stage
acceleration/deceleration), 11 (FRS: free-run stop), 12 (EXT: external trip), 13 (USP:
unattended start protection), 14: (CS: commercial power source enable), 15 (SFT: software
lock), 16 (AT: analog input voltage/current select), 17 (SET3: 3rd motor control), 18 (RS:
reset), 20 (STA: starting by 3-wire input), 21 (STP: stopping by 3-wire input), 22 (F/R:
forward/reverse switching by 3-wire input), 23 (PID: PID disable), 24 (PIDC: PID reset),
26 (CAS: control gain setting), 27 (UP: remote control UP function), 28 (DWN: remote
control DOWN function), 29 (DWN: remote control data clearing), 31 (OPE: forcible
operation), 32 (SF1: multispeed bit 1), 33 (SF2: multispeed bit 2), 34 (SF3: multispeed bit
3), 35 (SF4: multispeed bit 4), 36 (SF5: multispeed bit 5), 37 (SF6: multispeed bit 6),
38 (SF7: multispeed bit 7), 39 (OLR: overload restriction selection), 40 (TL: torque limit
enable), 41 (TRQ1: torque limit selection bit 1), 42 (TRQ2: torque limit selection bit 2),
43 (PPI: P/PI mode selection), 44 (BOK: braking confirmation)(*2), 45 (ORT:
orientation)(*2), 46 (LAC: LAD cancellation), 47 (PCLR: clearance of position deviation)(*2),
48 (STAT: pulse train position command input enable)(*2), 50 (ADD: trigger for frequency
addition [A145]), 51 (F-TM: forcible-terminal operation), 52 (ATR: permission of torque
command input)(*2), 53 (KHC: cumulative power clearance), 54 (SON: servo-on)(*2),
55 (FOC: pre-excitation)(*2), 56 (MI1: general-purpose input 1), 57 (MI2: general-purpose
input 2), 58 (MI3: general-purpose input 3), 59 (MI4: general-purpose input 4), 60 (MI5:
general-purpose input 5), 61 (MI6: general-purpose input 6), 62 (MI7: general-purpose input 7),
63 (MI8: general-purpose input 8), 64 (EMR: Emergency stop)(*1), 65 (AHD: analog command
holding), 66 (CP1: multistage position settings selection 1 )(*2), 67 (CP2: multistage position
settings selection 2)(*2), 68 (CP3: multistage position settings selection 3)(*2), 69 (ORL:
Zero-return limit function)(*2), 70 (ORG: Zero-return trigger function)(*2), 71 (FOT: forward drive
stop)(*2), 72 (ROT: reverse drive stop)(*2), 73 (SPD: speed / position switching)(*2), 74 (PCNT:
pulse counter), 75 (PCC: pulse counter clear), no (NO: no assignment)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00(NO) / 01(NC)
00 (RUN: running), 01 (FA1: constant-speed reached), 02 (FA2: set frequency overreached), 03 (OL:
overload notice advance signal (1)), 04 (OD: output deviation for PID control), 05 (AL: alarm signal),
06 (FA3: set frequency reached), 07 (OTQ: over-torque), 08 (IP: instantaneous power failure), 09 (UV:
undervoltage), 10 (TRQ: torque limited), 11 (RNT: operation time over), 12 (ONT: plug-in time over),
13 (THM: thermal alarm signal), 19 (BRK: brake release)(*2), 20 (BER: braking error)(*2), 21 (ZS: 0
Hz detection signal), 22 (DSE: speed deviation maximum)(*2), 23 (POK: positioning completed)(*2),
24 (FA4: set frequency overreached 2), 25 (FA5: set frequency reached 2), 26 (OL2: overload notice
advance signal (2)), 27 (Odc: Analog O disconnection detection), 28 (OIDc: Analog OI disconnection
detection), 29 (O2Dc: Analog O2 disconnection detection), 31 (FBV: PID feedback comparison),
32 (NDc: communication line disconnection), 33 (LOG1: logical operation result 1), 34 (LOG2: logical
operation result 2), 35 (LOG3: logical operation result 3), 36 (LOG4: logical operation result 4),
37 (LOG5: logical operation result 5), 38 (LOG6: logical operation result 6), 39 (WAC: capacitor life
warning)(*3), 40 (WAF: cooling-fan speed drop), 41 (FR: starting contact signal), 42 (OHF: heat sink
overheat warning), 43 (LOC: low-current indication signal), 44 (M01: general-purpose output 1),
45 (M02: general-purpose output 2), 46 (M03: general-purpose output 3), 47 (M04: general-purpose
output 4), 48 (M05: general-purpose output 5), 49 (M06: general-purpose output 6), 50 (IRDY: inverter
ready), 51 (FWR: forward rotation), 52 (RVR: reverse rotation), 53 (MJA: major failure), 54(WCO:
window comparator O), 55(WCOI: window comparator OI), 56 (WCO2: window comparator O2)
(When alarm code output is selected for "C062", functions "AC0" to "AC2" or "AC0" to "AC3" [ACn:
alarm code output] are forcibly assigned to intelligent output terminals 11 to 13 or 11 to 14,
respectively.)
00 (output frequency), 01 (output current), 02 (output torque), 03 (digital output frequency), 04 (output
voltage), 05 (input power), 06 (electronic thermal overload), 07 (LAD frequency), 08 (digital current
monitoring), 09 (motor temperature), 10 (heat sink temperature), 12 (general-purpose output YA0)
00 (output frequency), 01 (output current), 02 (output torque), 04 (output voltage), 05 (input power), 06
(electronic thermal overload), 07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature), 11
(output torque [signed value]), 13 (general-purpose output YA1)
00 (output frequency), 01 (output current), 02 (output torque), 04 (output voltage), 05 (input power), 06
(electronic thermal overload), 07 (LAD frequency), 09 (motor temperature), 10 (heat sink temperature), 14
(general-purpose output YA2)
×
[◯= Allowed
= Not permitted]
Default Setting
Setting
SJ700
during operation
L700
(allowed or not)
-FE(CE) -FU(UL)
-F(JP)
0.
×
0.
0.
0.
0.0
0.0
0.0
0.0
×
×
×
00
00
00
0.00
0.00
0.00
×
×
×
×
0.00
0.00
0.00
0.00
0.00
0.00
×
×
×
0.00
0.00
0.00
×
0.00
0.00
0.00
×
×
×
Rated current x 1.00
×
0.00
0.00
0.00
×
×
00
00
00
00
×
×
380/760
380/760
380/760
380/760
×
1.00
1.00
1.00
1.00
0.50
0.50
0.50
0.50
0.060
0.060
0.060
0.060
×
[◯= Allowed
= Not permitted]
Default Setting
Setting
SJ700
during operation
L700
(allowed or not)
-FE(CE) -FU(UL)
-F(JP)
18(RS)
18(RS)
18(RS)
18(RS)
×
×
16(AT)
16(AT)
16(AT)
16(AT)
06(JG)
06(JG)
06(JG)
03(CF2)
×
×
11(FRS)
11(FRS)
11(FRS)
02(CF1)
09(2CH)
09(2CH)
09(2CH)
01(RV)
×
03(CF2)
13(USP)
03(CF2)
06(JG)
×
×
02(CF1)
02(CF1)
02(CF1)
11(FRS)
01(RV)
01(RV)
01(RV)
13(USP)
×
×
00
00
00
00
00
00
00
00
×
×
00
00
00
00
00
00
00
00
×
00
00
00
00
×
00
01
00
00
×
00
00
00
00
×
00
00
00
00
×
00
00
00
00
×
01(FA1)
01(FA1)
01(FA1)
01(FA1)
×
00(RUN)
00(RUN)
00(RUN)
00(RUN)
×
03(OL)
03(OL)
03(OL)
03(OL)
×
07(OTO)
07(OTO)
07(OTO)
07(OTO)
×
40(WAF)
40(WAF)
40(WAF)
40(WAF)
×
05(AL)
05(AL)
05(AL)
05(AL)
×
00
00
00
×
00
00
00
00
00
×
×
00
00
00
00
Change
during operation
(allowed or not)
×
×
Change
during operation
(allowed or not)
18

Advertisement

Table of Contents
loading

This manual is also suitable for:

L700 series

Table of Contents