Fa1, Fa2: Frequency Arrival Signals; Run: Motor Running - Hitachi L100-004 HFE Manual

Table of Contents

Advertisement

FA1, FA2: Frequency arrival signals

Terminal function
A digital output configured as FA1 will be activated as soon as the set frequency has been reached. A digital
output configured as FA2 will stay activated at frequencies above those set under C 42 and C 43. In order to
provide for a certain amount of hysteresis during switching on and off, the FA1 and FA2 signals are activated
0.5Hz before the current frequency reaches the set value or the frequency set under C 42, respectively. The
FA1 and FA2 signals are then again deactivated 1.5Hz after the current frequency has passed the frequency
set under C 43.
FA1/FA2
FM
CM2
12
11
27V max.
50mA max.
Signal FA1
Configuration
C 21
C 22
C 42
1) If a programmable digital output is to be configured with FA2 output function, first of all a frequency
has to be set using C 42 at which the FA2 signal is to be activated during acceleration. Next a frequency
has to be set at which the FA2 signal is to be deactivated again, this is done using C 43.
2) Then configure under C 21 or C 22 one of the digital outputs 11 or 12 as FA1 or FA2 by entering the
parameter 01 for FA1 or 02 for FA2.
Remarks
• The transition of an FA1 or FA2 signal from the inactive to the active state is carried out with a delay of
approximately 60ms.

RUN: Motor running

Terminal function
A digital output configured as RUN stays activated as long as a frequency not equal to zero is sent to the
motor (i.e. as long as the motor is running in forward or reverse direction).
FM
12 11
CM2
27V max.
50mA max.
Configuration
C 21
C 22
Program one of the digital outputs 11 or 12 as RUN output by entering the parameter 00 under C 21 or C 22.
Set value (F 01)
Output frequency
1,5Hz
0,5Hz
0,5Hz
Signal active
60ms
C 43
RUN
Running command
at FW or RV
Output frequency
RUN signal
7-14
Chapter 7 – Control circuit terminal functions
Output frequency
Lt. C 42
Lt. C 43
Signal FA2
60ms
start frequency set under b 82
Signal active
0,5Hz
Signal active
60ms

Advertisement

Table of Contents
loading

Table of Contents