Protection and Automation Functions
7.2 Automatic Reclosing Function
[lovrkarc-130511-01.tif, 1, en_US]
Figure 7-52
7.2.4.19
Settings
Addr.
General
_:6601:1
_:6601:101
576
Cyclic Reclosing Function: Logic for the Functions of Reduced Dead Time and Dead-Line Check
Parameter
General:Mode
General:79 operating
mode
C
Setting Options
•
off
•
on
•
test
•
with op., w/o act. time
•
with op., with act. time
•
w.pickup, w/o act. time
•
w.pickup, w. action time
SIPROTEC 5, High-Voltage Bay Controller, Manual
Default Setting
on
with op., with
act. time
C53000-G5040-C015-9, Edition 11.2017