Logic
[locbsymm-100611-01.tif, 3, en_US]
Figure 8-21
The Threshold min/max parameter is the criterion by which unbalance in the phase currents is measured.
The device calculates the ratio between the minimum (I
Enter the lower limit of the maximum phase current (I
specifies the lower limit of the operating range of this function.
Delay failure indication
If it falls below the balance factor Threshold min/max and at the same time the maximum phase current
exceeds the Release threshold, the operate delay of the failure indication (parameter Delay failure
indication) begins. If both conditions persist during this time, the indication Failure is generated.
Blocking the Function
The following blockings reset the picked up function completely:
Externally or internally via the binary input signal
A protection pickup
The pickup signal of a protection function blocks the indication
8.3.8.4

Application and Setting Notes

Parameter: Threshold min/max
Recommended setting value (_:102) Threshold min/max = 0.5
The Threshold min/max parameter is used to set the ratio between the minimum (I
(I
) phase current.
max
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Logic Diagram of the Current-Balance Supervision
8.3 Supervision of the Secondary System
) and the maximum (I
min
max
) with the parameter Release threshold. This
max
>Block function
Failure .
Supervision Functions
) phase current.
) and the maximum
min
961