Information List

5.5.5
No.
Circuit break.
_:4261:500
_:4261:501
_:4261:502
_:4261:504
_:4261:503
_:4261:53
_:4261:58
_:4261:300
_:4261:301
_:4261:302
_:4261:303
_:4261:304
_:4261:306
_:4261:307
_:4261:308
_:4261:309
_:4261:310
_:4261:311
_:4261:312
_:4261:313
_:4261:317
_:4261:314
_:4261:315
_:4261:316
_:4261:322
_:4261:323

Trip Logic

5.5.6
5.5.6.1

Function Description

The Trip logic function block receives the group operate indication from the Protection function group or
Protection function groups and forms the protection trip command that is transmitted to the Circuit-breaker
function block.
The Circuit-breaker function block activates the device contact and thus causes the circuit breaker to open
(see
5.5.7 Circuit
The trip logic also decides when the protection trip command is reset (see
[loausbef-140113-01.tif, 1, en_US]
Figure 5-18
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Information
Circuit break.:>Ready
Circuit break.:>Acquisition blocking
Circuit break.:>Reset switch statist.
Circuit break.:>Reset AcqBlk&Subst
Circuit break.:External health
Circuit break.:Health
Circuit break.:Position
Circuit break.:Trip/open cmd.
Circuit break.:Close command
Circuit break.:Command active
Circuit break.:Definitive trip
Circuit break.:Alarm suppression
Circuit break.:Op.ct.
Circuit break.:ΣI Brk.
Circuit break.:ΣIA Brk.
Circuit break.:ΣIB Brk.
Circuit break.:ΣIC Brk.
Circuit break.:Break.-current phs A
Circuit break.:Break.-current phs B
Circuit break.:Break.-current phs C
Circuit break.:Tripping current 3I0/IN
Circuit break.:Break. voltage phs A
Circuit break.:Break. voltage phs B
Circuit break.:Break. voltage phs C
Circuit break.:CB open hours
Circuit break.:Operating hours
Breaker). The command output time is also effective here.
Trip Command
Function-Group Types
5.5 Function-Group Type Circuit Breaker, 3-Pole
Data Class
(Type)
SPS
SPS
SPS
SPS
ENS
ENS
DPC
SPS
SPS
SPS
SPS
SPS
INS
BCR
BCR
BCR
BCR
MV
MV
MV
MV
MV
MV
MV
INS
INS