Siemens 6MD85 Manual page 645

Siprotec 5 high-voltage bay controller
Hide thumbs Also See for 6MD85:
Table of Contents

Advertisement

Addr.
General
_:752:1
_:752:2
_:752:26
_:752:27
_:752:8
_:752:3
_:752:4
_:752:101
_:752:6
Dyn.s: AR off/n.rdy
_:752:28
_:752:35
Dyn.set: AR cycle 1
_:752:29
_:752:36
_:752:14
_:752:20
Dyn.set: AR cycle 2
_:752:30
_:752:37
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Parameter
C
Definite-T 2:Mode
Definite-T 2:Operate &
flt.rec. blocked
Definite-T 2:Dynamic
settings
Definite-T 2:Blk. w.
inrush curr. detect.
Definite-T 2:Method of
measurement
Definite-T 2:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
5 A @ 100 Irated 0.05 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Definite-T 2:Dropout
ratio
Definite-T 2:Dropout
delay
Definite-T 2:Operate
delay
Definite-T 2:Effect. by AR
off/n.ready
Definite-T 2:Stage
blocked
Definite-T 2:Effected by
AR cycle 1
Definite-T 2:Stage
blocked
Definite-T 2:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
5 A @ 100 Irated 0.05 A to 175.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Definite-T 2:Operate
delay
Definite-T 2:Effected by
AR cycle 2
Definite-T 2:Stage
blocked
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
Setting Options
off
on
test
no
yes
no
yes
no
yes
fundamental comp.
RMS value
0.010 A to 35.000 A
0.05 A to 175.00 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.90 to 0.99
0.00 s to 60.00 s
0.00 s to 60.00 s
no
yes
no
yes
no
yes
no
yes
0.010 A to 35.000 A
0.05 A to 175.00 A
0.001 A to 1.600 A
0.002 A to 8.000 A
0.00 s to 60.00 s
no
yes
no
yes
Default Setting
off
no
no
no
fundamental
comp.
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
0.95
0.00 s
0.30 s
no
no
no
no
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
0.30 s
no
no
645