Function-Group Types
5.1 Power-System Data
Addr.
_:8881:127
_:8881:130
CT phases
_:8881:101
_:8881:102
_:8881:117
_:8881:118
_:8881:116
_:8881:114
_:8881:107
_:8881:108
_:8881:109
CT IN
_:8881:104
_:8881:105
_:8881:119
_:8881:120
CT IN2
_:8881:106
_:8881:113
_:8881:121
_:8881:122
CT 1
_:3841:103
190
Parameter
CT 3-phase:Tracking
CT 3-phase:Measuring-
point ID
CT 3-phase:Rated primary
current
CT 3-phase:Rated secon-
dary current
CT 3-phase:Current range
CT 3-phase:Internal CT type
CT 3-phase:Neutr.point in
dir.of ref.obj
CT 3-phase:Inverted phases
CT 3-phase:CT error
changeover
CT 3-phase:CT error A
CT 3-phase:CT error B
CT 3-phase:Rated primary
current
CT 3-phase:Rated secon-
dary current
CT 3-phase:Current range
CT 3-phase:Internal CT type
CT 3-phase:Rated primary
current
CT 3-phase:Rated secon-
dary current
CT 3-phase:Current range
CT 3-phase:Internal CT type
CT 1:Magnitude correction
C
Setting Options
•
inactive
•
active
0 to 100
1.0 A to 100000.0 A
•
1 A
•
5 A
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
•
CT protection
•
CT measurement
•
no
•
yes
•
none
•
AC
•
BC
•
AB
1.00 to 10.00
0.5 % to 50.0 %
0.5 % to 50.0 %
1.0 A to 100000.0 A
•
1 A
•
5 A
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
•
CT protection
•
CT measurement
1.0 A to 100000.0 A
1 A to 5 A
•
1.6 x IR
•
8 x IR
•
20 x IR
•
100 x IR
•
CT protection
•
CT measurement
0.010 to 10.000
SIPROTEC 5, High-Voltage Bay Controller, Manual
Default Setting
active
0
1000.0 A
1 A
100 x IR
CT protection
yes
none
1.00
5.0 %
15.0 %
1000.0 A
1 A
100 x IR
CT protection
1000.0 A
1 A
1.6 x IR
CT protection
1.000
C53000-G5040-C015-9, Edition 11.2017