Control Functions
6.5 Switching Sequences
[dwswseq1-110913-01.vsd, 1, en_US]
Figure 6-99
Starting and Canceling a Switching Sequence
One of the following methods can be used to start a switching sequence:
•
On-site operation: menu or display page
•
Input
>Start during rising edge, for example, via binary input
•
Controllable
•
Input
>Start via a function key
•
Controllable
One of the following methods can be used to cancel a switching sequence:
•
On-site operation: menu or display page
•
Input
>Cancel during rising edge, for example, via binary input
•
Controllable
DNP
•
Input
>Cancel via a function key
•
Controllable
On-Site Operation
If at least one Switching sequence function block is used in the device, a new Switching sequences entry is
shown in the first line of the Control menu. If this menu item is selected, an overview of all switching
sequences and the current status will be displayed (see
You can start or cancel the switching sequences from this menu.
426
Switching Sequence Function Block
Start for the start via a communication protocol, for example, IEC 61850, T103, or DNP
Start via a function key
Cancel for the cancelation via a communication protocol, for example, IEC 61850, T103, or
Cancel via a function key
Figure
6-100, example with 2 switching sequences).
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017